BS 7870-4.10:2011+A1:2016
LV and MV polymeric insulated cables for use by distribution and generation utilities Specification for distribution cables with extruded insulation of rated voltages of 11 kV to 33 kV
| Označení normy: | BS 7870-4.10:2011+A1:2016 |
| Počet stran: | 32 |
| Vydáno: | 2016-06-30 |
| ISBN: | 978 0 580 93805 4 |
| Status: | Standard |
BS 7870-4.10:2011+A1:2016
This standard BS 7870-4.10:2011+A1:2016 LV and MV polymeric insulated cables for use by distribution and generation utilities is classified in these ICS categories:
- 29.060.20 Cables
This section of BS 7870 specifies requirements for the construction, dimensions and mechanical and electrical properties of 6.35/11(12) kV to 19/33(36) kV single-core cables having either aluminium or copper conductors, cross-linked polyethylene (XLPE) or ethylene propylene rubber (EPR) extruded insulation, a copper wire metallic screen and an oversheath of one of the following compounds:
medium density polyethylene (MDPE) compound type DMP 5 (Type A cables);
thermoplastic compound type DMZ 4 for cables with having a low emission of smoke and corrosive gases when affected by fire (Type B cables).
The standard also specifies requirements for 11 kV cables laid up in a triplex formation.
This section of BS 7870 is applicable to cables that are designed for a maximum continuous conductor operating temperature of 90 °C and for a maximum short-circuit conductor temperature of 250 °C.