BS 7870-4.10:2011+A1:2016 LV and MV polymeric insulated cables for use by distribution and generation utilities Specification for distribution cables with extruded insulation of rated voltages of 11 kV to 33 kV

BS 7870-4.10:2011+A1:2016

LV and MV polymeric insulated cables for use by distribution and generation utilities Specification for distribution cables with extruded insulation of rated voltages of 11 kV to 33 kV

Formát
Dostupnost
Cena a měna
Anglicky Zabezpečené PDF
K okamžitému stažení
6240 Kč
Anglicky Tisk
Skladem
6240 Kč
Označení normy:BS 7870-4.10:2011+A1:2016
Počet stran:32
Vydáno:2016-06-30
ISBN:978 0 580 93805 4
Status:Standard
Popis

BS 7870-4.10:2011+A1:2016


This standard BS 7870-4.10:2011+A1:2016 LV and MV polymeric insulated cables for use by distribution and generation utilities is classified in these ICS categories:
  • 29.060.20 Cables

This section of BS 7870 specifies requirements for the construction, dimensions and mechanical and electrical properties of 6.35/11(12) kV to 19/33(36) kV single-core cables having either aluminium or copper conductors, cross-linked polyethylene (XLPE) or ethylene propylene rubber (EPR) extruded insulation, a copper wire metallic screen and an oversheath of one of the following compounds:

  1. medium density polyethylene (MDPE) compound type DMP 5 (Type A cables);

  2. thermoplastic compound type DMZ 4 for cables with having a low emission of smoke and corrosive gases when affected by fire (Type B cables).

The standard also specifies requirements for 11 kV cables laid up in a triplex formation.

This section of BS 7870 is applicable to cables that are designed for a maximum continuous conductor operating temperature of 90 °C and for a maximum short-circuit conductor temperature of 250 °C.

NOTE Information to be supplied by the purchaser, and items to be agreed between the purchaser and the manufacturer at the time of enquiry and/or order are given in Annex B. Guidance on type testing is given in Annex C.