Vážení zákazníci, v letošním roce budeme expedovat poslední objednávky ve čtvrtek 18. 12. 2025.

Těšíme se s vámi na shledanou od pondělí 05. 01. 2026.

 

Cena s DPH / bez DPH
>IEC 61439-5:2023 - Low-voltage switchgear and controlgear assemblies - Part 5: Assemblies for power distribution in public networks
sklademVydáno: 2023-05-04

IEC 61439-5:2023

Low-voltage switchgear and controlgear assemblies - Part 5: Assemblies for power distribution in public networks

Ensembles d'appareillage à basse tension - Partie 5: Ensembles pour réseaux de distribution publique

Formát
Dostupnost
Cena a měna
Anglicky/Francouzsky Tisk
skladem
7150 Kč
Anglicky/Francouzsky PDF
K okamžitému stažení
Tisknutelné
7150 Kč
Označení normy:IEC 61439-5:2023
Vydáno:2023-05-04
Edice:3
ICS:29.130.20
Počet stran (Anglicky/Francouzsky):77
ISBN (Anglicky/Francouzsky):9782832269398
Popis

IEC 61439-5:2023

IEC 61439-5:2023 defines the specific requirements for public electricity network distribution assemblies (PENDAs). PENDAs have the following criteria:
- used for the distribution of electrical energy in three phase systems for which the rated voltage does not exceed 1 000 V AC (see Figure 101 for a typical distribution network) and DC systems not exceeding 1 500 V DC;
- stationary;
- open type assemblies are not covered by this document;
- suitable for installation in places where only skilled persons have access for their use, however, outdoor types can be installed in situations that are accessible to ordinary persons
- intended for use in energy distribution in public power grids;
- indoor use: assemblies for installation inside of electric power substations;
- outdoor use: assemblies containing an enclosure suitable for open air installation.
This third edition cancels and replaces the second edition published in 2014. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) omission of the requirement to conduct mechanical tests at -25 °C when enclosures are made of a metallic material;
b) addition of assumed loading factors generation supplies and electric vehicle charging applications;
c) additional dielectric tests when a PENDA is used in a distribution substation with separate HV and LV earths;
d) further clarification of representative samples for design verification.
The content of the corrigendum 1 (2025-02) has been included in this copy.